Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Still deciding? Get samples of US$ 280.99/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL | P1K(L) | P2K(L) | P3K(L) | ||
PHASE | Single phase with ground | ||||
CAPACITY | 1000VA/ 800W | 2000VA/ 1600W | 3000VA / 2400W | ||
INPUT | |||||
Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | ||||
Input Voltage Range | 55~150 VAC or 110-300VAC at 50% load 85-140 VAC or 160-280VAC at 100% load | ||||
Frequency Range | 40Hz ~ 70Hz | ||||
Power Factor | >=0.99@ Nominal voltage(100% load) | ||||
OUTPUT | |||||
Output Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | ||||
Voltage Regulation | ±1% | ||||
Frequency Range(Synchronized Range) | 47-53 Hz or 57~63 Hz | ||||
Frequency Range(Batt. Mode) | 50 Hz±0.25Hz or 60Hz±0.3 Hz | ||||
Current Crest Ratio | 3 : 1 | ||||
Harmonic Distortion | <=3% THD(Linear Load), <=6% THD(Non-linear Load) | ||||
Transfer Time |
AC to DC | Zero | |||
Inverter to Bypass | 4ms(Typical) | ||||
Waveform(Batt. Mode) | Pure Sine wave | ||||
EFFICIENCY | |||||
To AC Mode | 88% | 88% | 90% | ||
To Battery Mode | 83% | 85% | 88% | ||
BATTERY | |||||
Standard Model |
Battery Type | 12V/7Ah | 12V/7Ah | 12V/7Ah | |
Numbers | 2 | 4 | 6 | ||
Typical Recharge Time | 4 hours recover to 90% capacity | ||||
Charging Current(max.) | 1.0A | ||||
Charging Voltage | 27.4VDC±1% | 54.7VDC±1% | 82.1VDC±1% | ||
Long-run Model |
Battery Numbers | Depending on the capacity of external batteries | |||
Charging Current(max.) | 1A-6A(Adjustable) | ||||
Charging Voltage | 41.0VDC±1% | 82.1VDC±1% | 109.4VDC±1% | ||
INDICATORS | |||||
LCD | Load level, Battery level, AC mode, Bypass mode, and Fault indicators | ||||
PHYSICAL | |||||
Standard Model |
Dimension, D×W×H(mm) | 397×145×220 | 419×190×318 | ||
Net Weight(kgs) | 9.8 | 17 | 23 | ||
Long-run Model |
Dimension ,D×W×H(mm) | 282×145×220 | 397×145×220 | ||
Net Weight(kgs) | 3.97 | 6.7 | 7.24 | ||
ENVIRONMENT | |||||
Humidity | 20-90% RH@ 0-40ºC(Non-condensing) | ||||
Noise Level | Less than 50dBA@ 1 Meter | ||||
MANAGMENT | |||||
Smart RS-232/USB | Support Windows@2000/2003/XP/Vista/2008, Windows@7/8, Linux, Unix, and MAC | ||||
Optional SNMP | Power management from SNMP manager and web browser |
MODEL | P6K(L) | P10K(L) | ||
PHASE | Single phase with ground | |||
CAPACITY | 6000VA/ 4800W | 10000VA / 8000W | ||
INPUT | ||||
Nominal Voltage | 208/220/230/240VAC | |||
Input Voltage Range | 110-300 VAC at 50% load ,178-300 VAC at 100% load | |||
Frequency Range | 46~54Hz or 56~64Hz | |||
Power Factor | >=0.99@ Nominal voltage(100% load) | |||
OUTPUT | ||||
Output Voltage | 208/220/230/240VAC | |||
Voltage Regulation | ±1% | |||
Frequency Range(Synchronized Range) | 46~54 Hz or 56-64 Hz | |||
Frequency Range(Batt. Mode) | 50 Hz or 60Hz ±0.1 Hz | |||
Current Crest Ratio | 3 : 1 | |||
Harmonic Distortion | <=3% THD(Linear Load), <=5% THD(Non-linear Load) | |||
Transfer Time |
AC to DC | Zero | ||
Inverter to Bypass | Zero | |||
Waveform(Batt. Mode) | Pure Sine wave | |||
EFFICIENCY | ||||
To AC Mode | 92% | 90% | ||
To Battery Mode | 90% | 89% | ||
BATTERY | ||||
Standard Model |
Battery Type | 12V/7Ah | ||
Numbers | 16 | |||
Typical Recharge Time | 9 hours recover to 90% capacity | |||
Charging Current(max.) | 1.0A | |||
Charging Voltage | 218.4VDC±1% | |||
Long-run Model |
Battery Numbers | Depending on the capacity of external batteries | ||
Charging Current(max.) | 1A, 2A, 4A, 6A(Adjustable) | Default:4.0A± 10% | ||
Charging Voltage | 218.4VDC±1% | |||
INDICATORS | ||||
LCD | Load level, Battery level, AC mode, Bypass mode, and Fault indicators | |||
PHYSICAL | ||||
Standard Model |
Dimension,D×W×H(mm) | 369×190×688 | 442×190×688 | |
Net Weight(kgs) | 60 | 66 | ||
Long-run Model |
Dimension,D×W×H(mm) | 369×190×318 | 442×190×318 | |
Net Weight(kgs) | 12 | 16 | ||
ENVIRONMENT | ||||
Humidity | 0-95% RH@ 0-50ºC(Non-condensing) | |||
Noise Level | Less than 58dBA@1 Meter | |||
MANAGMENT | ||||
Smart RS-232/USB | Support Windows@2000/2003/XP/Vista/2008, Windows@7/8, Linux, Unix, and MAC | |||
Optional SNMP | Power management from SNMP manager and web browser |
MODEL | 3P10KL | 3P15KL | 3P20KL | ||
PHASE | 3- phase in/ 1-phase out | ||||
CAPACITY | 10000VA/ 8000W | 15000VA/ 12000W | 20000VA / 16000W | ||
INPUT | |||||
Input Voltage Range | 305~478 VAC (3-phase) at 100% load 190-520 VAC ( 3-phase) at 50% load | ||||
Frequency Range | 46-54Hz or 56-64Hz | ||||
Power Factor | >=0.99@ Nominal voltage(100% load) | ||||
OUTPUT | |||||
Output Voltage | 208/220/230/240VAC | ||||
Voltage Regulation | ±1% | ||||
Frequency Range(Synchronized Range) | 46-54 Hz or 56~64 Hz | ||||
Frequency Range(Batt. Mode) | 50 Hz±0.1Hz or 60Hz±0.1 Hz | ||||
Current Crest Ratio | 3 : 1 | ||||
Harmonic Distortion | <=2% THD(Linear Load), <=5% THD(Non-linear Load) | ||||
Transfer Time |
AC to DC | Zero | |||
Inverter to Bypass | Zero | ||||
Waveform(Batt. Mode) | Pure Sine wave | ||||
EFFICIENCY | |||||
To AC Mode | 89% | 89% | 89% | ||
To Battery Mode | 86% | 88% | 87% | ||
BATTERY | |||||
Long-run Model |
Battery Numbers | Depending on the capacity of external batteries | |||
Charging Current(max.) | 4A | 4A | |||
Charging Voltage | 218.4VDC±1% | ||||
INDICATORS | |||||
LCD | UPS status, Load level, Battery level, Input / Output voltage, Discharge timer, and Fault indicators | ||||
PHYSICAL | |||||
Long-run Model |
Dimension ,D×W×H(mm) | 592×250×576 | 592×250×576 | ||
Net Weight(kgs) | 28 | 40 | 40 | ||
ENVIRONMENT | |||||
Humidity | 20-90% RH@ 0-40ºC(Non-condensing) | ||||
Noise Level | Less than 50dBA@ 1 Meter | ||||
MANAGMENT | |||||
Smart RS-232/USB | Support Windows@2000/2003/XP/Vista/2008, Windows@7/8, Linux, Unix, and MAC | ||||
Optional SNMP | Power management from SNMP manager and web browser | ||||
*Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC. |